MOSAIC MOR4C

Safety relay expansion units with configurable Outputs

4 single channel outputs (safety category 1 or 2); or 2 dual channel outputs (safety category 4)

Clamp contacts


Betreff: MOSAIC MOR4C


General data

Type designation
MOSAIC MOR4C

Safety data

PFHd (EN ISO 13849)
2,9E-9
SIL (acc. IEC 62061)
SIL 3 - SILCL 3 according to IEC 61508 - IEC 62061 / PL e - Cat. 4 according to ISO 13849-1

Environmental conditions

Max. storage temperature
−20… +85 °C
Max. operating temperature
-10 ... +55 °C

Electrical data

Inputs for start/restart and external equipment monitoring
4
Connection to MSC bus
Yes

Mechanical data

Dimensions
Height
99 mm
Width
22,5 mm
Length
114 mm
Mounting
Rail fastening according to EN 50022-35 standard